Grüntek Energy SolutionsGrüntekENERGY SOLUTIONS

SOLUTION · 04

PICVs & hydronic balancing
Right flow at every unit. At every load.

Conversion of 3-way and 2-way valve systems to pressure-independent control valves (PICVs) on AHUs and FCUs, with selection, installation, commissioning and flow verification, so the chilled-water network holds its design ΔT at part load with reduced pumping. We supply and install the full Danfoss PICV range for chilled-water buildings, from FCUs and AHUs to ETS heat exchangers.

WHAT WE DELIVER

PICVs & hydronic balancing

Conversion of 3-way and 2-way valve systems to pressure-independent control valves (PICVs) on AHUs and FCUs, with selection, installation, commissioning and flow verification, so the chilled-water network holds its design ΔT at part load with reduced pumping.

3-way to PICV conversion

Replacing 3-way valves so chilled water is no longer bypassed back to the return, which is one of the most common causes of low ΔT.

2-way and DRV to PICV upgrade

Balanced 2-way systems work at design conditions but drift at part load. PICVs hold each unit on its required flow whatever the pressure.

Danfoss PICV selection and sizing

Danfoss PICVs and actuators selected for each unit from its design flow, from small FCU valves to AHUs and ETS heat exchangers.

Installation in occupied buildings

Phased floor by floor, using techniques such as pipe freezing where a section has to be isolated, to keep disruption to a minimum.

Commissioning and flow verification

Flow settings are set and verified at each unit, and the results are documented at handover.

Pump and DP setpoint optimisation

Once flows are under control, the pump differential-pressure setpoint can be reviewed so the pumps slow down at part load.

SEE THE DIFFERENCE

Balanced 2-way valves vs PICVs,
floor by floor.

Switch between a 2-way valve system balanced with DRVs and PICVs, at full and part load, to see what happens to flow, ΔT and the pump. Most buildings spend most of the year at part load.

Valves
Building load
Plant roomFloor 1Load 55%Lobby AHUHigher ΔP4.3 L/s / 5.0 designΔT 5.7°COver-flowFloor 2Load 40%Office FCUsHigher ΔP0.7 L/s / 1.5 designΔT 7.5°COver-flowFloor 3Load 35%Office FCUsDesign ΔP0.5 L/s / 1.5 designΔT 8.9°COn targetFloor 4Load 30%Office FCUsLower ΔP0.4 L/s / 1.5 designΔT 10.3°CUnder-flowRoofLoad 65%Fresh-air AHULower ΔP1.8 L/s / 3.5 designΔT 11.5°CUnder-flowPump 78%Supply 5.5°CReturn 13.2°C
Swipe to see the whole riser →SupplyReturnPipe thickness follows flow; dash speed follows flow against design

2-way valves with DRVs · Part load

Pump speed78%
Total flow7.6 L/s
System ΔT7.7°C
Pump power (of design)36%

At part load, the 2-way valves close and the pressure across each branch changes. Flow through a valve follows Q = Kv × √ΔP, so units near the pump see extra pressure and over-flow, while units at the end of the riser under-flow. The DRV settings only hold at design conditions, so ΔT drops and the pump moves more water at a higher pressure than the load needs.

Q = Kv × √ΔP

At part load

Pump power
36% → 23%
System ΔT
7.7°C → 8.9°C
Total flow
7.6 → 6.6 L/s
Units off target
4 → 0

2-way + DRV → PICV

Illustrative model of one riser with a typical mix of AHUs and FCUs, both options on a variable-speed pump, using Q = Kv × √ΔP, pump affinity laws and simplified coil behaviour. It is not a savings estimate. Every building is different, so we measure yours.

How a PICV upgrade runsFrom the existing valves to verified flows.
  1. SurveyValves, units and pumps
  2. SelectSize each valve to its unit
  3. InstallPhased, minimal disruption
  4. VerifySet and check every flow
  5. OptimiseReview the pump DP setpoint

RELATED WORK

Projects in this area.

All projects

PRODUCTS & PLATFORMS

What we use.

Danfoss AB-QM pressure-independent control valves.
Danfoss AB-QM pressure-independent control valves.
  • Danfoss

Danfoss products

Danfoss products for your project.

Product details
Representative HVAC pumping installation.
Representative HVAC pumping installation.

Chilled-water pumps & VFDs

Equipment for pumping and fan systems.

Product details

Keep it performing with an AMC.

Comprehensive and non-comprehensive AMCs for chillers, condensing units, HVAC, ETS, BMS and metering.

FAQ

Common questions.

What is a PICV and why does it matter?

A pressure-independent control valve holds each unit at the flow it needs, whatever the pressure in the pipework. A system balanced with 2-way valves and DRVs performs well at full load, but its settings only hold at design conditions. At part load, flow through each valve follows Q = Kv × √ΔP, so as pressures shift some units over-flow and others under-flow. That lowers ΔT and makes the pumps move more water than the load needs. PICVs keep every unit on its required flow with reduced pumping.

Do PICVs work with our existing pumps?

Yes. They improve balance and ΔT on their own, and the pumping benefit is largest when the pumps also run at variable speed. We assess the pumps and controls as part of the survey.

What about buildings with 3-way valves?

3-way valves send unused chilled water straight back to the return, which lowers ΔT at part load. Converting them to PICVs, together with variable-speed pumping, is usually one of the first measures we look at.

Does a PICV upgrade help with Delta-T charges?

It addresses one of the main causes of low ΔT. Whether it is enough on its own depends on the building, so we measure first. See our Delta-T rectification plans.

Let’s talk about your building.

Contact our team